Abstract: 
Fault currents are identified as the reason for the poor quality of supply in a power system. The
circuit breakers are the most dynamic and transient equipment in transmission and distribution
power systems and they are the main interrupter for the clearing of faults. In the power system,
95% of faults occur in the medium voltage network. If a faults occurs and is not interrupted
timeously by the circuit breaker, the entire system ages faster.
It was identified that the arcing temperature during fault interruption is most responsible for the
wearing of the circuit breaker arcing contacts, thus, leading to the reduced breaker lifespan. The
useful life improvement was dependant on the reduction of the arcing current and power of the
arc which is proportional to the arcing energy and temperature. The vacuum circuit breaker was
investigated for the controlled switching technologies. A predicted controlled trip time logic
equation was derived using the controlled switching methodology with the addition of using
input parameter variables relevant to the circuit breaker environment to predict early current zero
tripping. The environmental conditions comprised of the ambient temperature, idle time and
standard circuit breaker operation time. The advanced controlled circuit breaker logic was also
developed using electromagnetic transient simulation software called PSCAD to predict the
earlier current zero tripping times based on the vacuum circuit breakers environmental
conditions. The software uses the black box modules to mimic operation of each environmental
condition namely the idle time logic controller, temperature delay logic controller and predicted
current zero controller. The results for the predicted controlled trip time equation was compared
to the results obtained using the simulated results on PSCAD.
The results from the predicted controlled trip equation versus the simulated advanced controlled
simulated module proved to be within a 0.1% tolerance. The PSCAD software also facilitated
the analysis of results for the various interruption phenomena namely the namely arc voltage,
arc current, transient recovery voltage, re-ignition, restrikes, dynamism and temperature of arc
that occur during the circuit breaker fault interruption. The abovementioned interruption had
seen a reduction when compared to the conventional circuit breaker during fault interruption
with the average arc current being reduced by 10%. The advanced controlled simulated results
obtained for the interruption phenomena was thereafter benchmarked against the simulated
conventional vacuum circuit breaker using the Arrhenius equation to determine its impact on the
circuit breaker useful life.
The results for the advanced controlled switching circuit breaker had proven an average of 7%
improvement in useful life when compared to a conventional circuit breaker. The 7%
improvement proved to increase the circuit breaker lifespan for an average of 20 years to 21.4 years. This is a 1.4-year improvement in the circuit breaker lifespan. Thus, the cost of
replacement of the circuit breaker may be deferred by 1.4 years but this has a significant impact
on the total annual capital expenditure budget due to the number of circuit breakers used.
Description: 
A dissertation submitted in fulfilment of the requirements for the Master of Electrical Power Engineering, Durban University of Technology, 2022.
URI: https://hdl.handle.net/10321/4361
DOI: https://doi.org/10.51415/10321/4361
Appears in Collections:Theses and dissertations (Engineering and Built Environment)

Files in This Item:
File Description SizeFormat
Nadeem_GH_2022.pdfThesis3.33 MBAdobe PDFView/Open
Show full item record

Page view(s)

310
checked on Dec 22, 2024

Download(s)

324
checked on Dec 22, 2024

Google ScholarTM

Check

Altmetric

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.